A PRELIMINARY ASSESSHENT OF CISTERN WATER QUALITY IN - SELECTED KROTELS AND GUEST HOUSES IN THE U.S. VIRGIN ISLANDS Robert H. Ruskin and J. Hari Krishna Water Resources Research Center University of the Virgin Islands St. Thomas, VI 60802 Technical Report No. 34 Project No: 02 Grant. Award No: 14-08-0001-G15935 July 1990 The research on which this report is based, was financed in part by the United States Department of the Interior, Geological Survey as authorized by the Water Research “and Development Act of 1984 (PL 98-242). Contents of this publication do not necessarily reflect the views and policies of the United States Department of the Interior, nor does the mention of trade names or commercial products constitute their endorsement by the United States Government. The authors of this repert wish to emphasize that the results of the study are only preliminary, and no generalized inferences should be drawn based upon this report. . ABSTRACT Tourism is the most important industry in the Virgin Islands, which brings in millions of dollars of revenue to the local government. …

Download the original document · Plain text (TXT) · Browse the archive · How this archive works

Original source: https://www.uvi.edu/files/documents/Research_and_Public_Service/WRRI/Cistern_Water_Quality_in_Selected_Hotels.pdf

SHA-256 9c72f18abefb806ab4405f778f15de0f0581d752ff6e4d44bd63b5a90651872f

Re-using this document

Our description, tagging, arrangement, extracted text and machine transcripts are released under CC0 1.0. We assert nothing about the document itself.

Archive identifier LF-9c72f18abefb

Document text

A PRELIMINARY ASSESSHENT OF CISTERN WATER QUALITY IN - SELECTED KROTELS AND GUEST HOUSES IN THE U.S. VIRGIN ISLANDS Robert H. Ruskin and J. Hari Krishna Water Resources Research Center University of the Virgin Islands St. Thomas, VI 60802 Technical Report No. 34 Project No: 02 Grant. Award No: 14-08-0001-G15935 July 1990 The research on which this report is based, was financed in part by the United States Department of the Interior, Geological Survey as authorized by the Water Research “and Development Act of 1984 (PL 98-242). Contents of this publication do not necessarily reflect the views and policies of the United States Department of the Interior, nor does the mention of trade names or commercial products constitute their endorsement by the United States Government. The authors of this repert wish to emphasize that the results of the study are only preliminary, and no generalized inferences should be drawn based upon this report. . ABSTRACT Tourism is the most important industry in the Virgin Islands, which brings in millions of dollars of revenue to the local government. Since maintaining good water quality is important for tourism, an attempt was made in this preliminary study to assess the bacteriological quality of cistern water in selected hotels, resorts, and guest houses on St. Thomas, U.S. Virgin Islands. Our results indicate considerable variability in cistern water quality between different hotels and guest houses. Those establishments that maintained close supervision with regard to disinfection procedures maintained water quality that was acceptable under the Safe Drinking Water standards. There were, however, other establishments which were unable to provide water of acceptable quality for drinking purposes. While total coliform count and turbidity are the established indicators of cistern water quality at the present time, testing for fecal coliforms and Pseudomonas aeruginosa may be more appropriate to ensure the safety of cistern water in the Virgin Islands. ACKNOWLEDGEMENTS We gratefully acknowledge and appreciate the cooperation of many hotel and guest house owners and/or operators who participated in this study. Their interest and assistance made this study possible. Thanks are also due to the staff of the Caribbean Research Institute for assistance with the preparation of this report. Our appreciation to Ms. Annelise Knudsen and her staff at the Virgin Islands Water and Power Authority Laboratory for keeping us supplied with laboratory grade water when our system failed. ii TABLE OF CONTENTS Page ADSUraCt Lecce ce cee nce cen ee ete tee eee seen ee . i Acknowledgements 2... ccc eee eee ec er eee twee eee e eee Li Table of ContentS ..... eee ee ee eee wee eee iii INtKOduction 2. ec eee ee eee ew cee eee cent eeeee 1 Materials and Methods §..........e2 eee ee ce bce ueveee 5 Site selection Lo. cece cece cc cee eee tee ee tte ee 5 Sample collection procedures ...... ee ec ee ee eee 8 Physical chemical analyseS .... cs. eee eee cece ces 8 Microbiological analySeS ..... cc cee eee eee eet 9 Pseudomonas aeruginosa analysiS .......e2ee000- 10 Verification of isolates 2... eee cee ee ee eee 10 Results ....... Cee ee ee ee ee mee ee ee eee ee ee we eee 12 DISCUSSION 2... cee ec eee ewe eee eee tees sea ced euleee ae 22 SUMMALY 2 eee ec cee ee cee w er ee renee eer vee erecces eee ene 25 Recommendations .e ec c cee eee wcrc eee nee ee eee ete ences 26 Bibliography ... ec eee eee ce eee eee eee eee eee teens 27 APPENdGICeS Loewe ec eee cee ence ee cee eee ewe tee ee ee wee ees 31 Dates of Sampling for Each Cistern ........ waee 32 Range of Counts for Different Bacterial Indicators ......... a 33 Chlorine Residual in Water Samples ........ eee 34 Lil INTRODUCTION The number one industry in the Virgin Islands is tourism, which brings in millions of dollars of revenue to the local government. On St. Thomas there are six hotels with more than 100 rooms; however, an estimated 75 percent of all lodging places have 50 or fewer rooms. The mountainous terrain makes water distribution. a problem. The solution has been the development of cistern water systems. Under the Virgin Islands Code, every building (except for federal buildings which are exempt from the local code) must have its own cistern. This includes all hotels and guest houses. These cisterns range from small 1,500 gallon cisterns for small residential cottages, to a large 700,000 gallon system which supplies all the water needs of a hotel complex in St. Thomas. As part of an ongoing investigation into cistern water quality in the territory, we focused on cistern water quality of a few randomly selected hotels “and guest. houses on St. Thomas for purposes of comparing the results to the Safe Drinking Water Standards (SDWS). The results are to be used to assess if those standards are the best ones to use for cistern water systems, or whether standards specific for such systems should be established. While cisterns may vary in size and construction, as well as the type of water they may hold (rain, trucked in, potable, well water, and RO/distilled water), all cisterns share some common features which set them apart from a potable water supply. These include being exposed to the environment, thus subjected to external contamination; and being built in conjunction with a roof-top collection system for the harvesting of rainfall. Hotels and guest houses (Inns) in the Virgin Islands are mandated under the Safe Drinking Water Act of 1974 and as amended in 1986 to have their water tested on a quarterly basis. Currently, only the total coliform count and turbidity of the sample are required under the Safe Drinking Water Act (SDWA) of 1974 and as amended in 1986. If the sample contains more than 1 total coliform per 100 mL, and/or has a turbidity greater than 1.0 NTU, the sample is in violation of the mandates of the Safe Drinking Water Standards (SDWS). Next year additional tests will be required. In the event a sample tests positive for total coliforms, repeat samples must be collected within 24 hours of notification, in addition the total coliform positive sample must be analyzed for fecal coliforms or E. coli. Finally the hotel must maintain a disinfectant residual at all times of no less than 0.2 mg/L; in lieu of this the hotel may substitute heterotrophic plate counts (Standard Plate Count). If the count does not exceed 500 total organisms per mL, the system is considered to have a "detectable" residual for compliance purposes. Systems in violation of this requirement must install filtration unless the State determines that the violation was not caused by a deficiency of treatment of the source water (34). The standards for pH and conductivity are more aesthetic than practical and are rarely enforced. The pH should be as close to neutral as possible between 6.5 - 8.5. Total. dissolved solids (TDS) which cause conductivity, should be less than 500 mg/L. The total coliform bacteria has been the indicator of choice in determining potable water quality since 1914 (4). Since coliforms are frequently associated with fecal contamination, the presence of coliforms in a potable water supply indicates that the supply has been contaminated. As the number of coliforms increase, so does the probability of encountering enteric pathogens since there is a high degree of correlation between coliforms and enteric pathogens (4,5,24). In two previous cistern studies we found that 74 percent of the samples from privately owned cisterns, and 49 percent of the samples from public housing cisterns were not. in compliance with the Safe Drinking Water Standards. The environment in which the cisterns are in close contact with has an abundance of coliform bacteria (11,14,19,28,29) which are not necessarily cf human origin. They are frequently present in the leaf debris, dust, soil deposits, and animal droppings which may have accumulated on the roof and in the gutters (11,28,29). Also, the total coliform standard does not adequately predict the occurrence of Pseudomonas aeruginosa, a naturally occurring opportunistic pathogen found in soil and water (13,25); our studies show that there is no correlation between it and the total coliform (16,29). Indeed in both of the studies mentioned before, Ps. aeruginosa was found in 69 percent and 49 percent of the private residential and public housing cisterns respectively, with it being present in the absence of total coliform almost 16 percent of the time on average. While most Virgin Islanders drink their own cistern water, with many claiming to suffer no ill effects, visitors may not be immune since most of them come from large cities where drinking water is usualiy treated and protected from external contamination. In this study, we attempted to make a preliminary assessment of cistern water quality in selected hotels and guest houses on St. Thomas in relation to the Safe Drinking Water Standards as set by the U.S. Environmental Protection Agency. In addition we determined the relative occurrence of the opportunistic pathogen Pseudomonas aeruginosa occurring in hotel and guest house cisterns and compared it to free chlorine residual. This study was also used to gather data upon which to base recommendations for alternate regulations for cistern stored. water. MATERIALS AND METHODS Site selection. Initially 23 hotels and guest houses (Inns) were chosen for screening in the pilot phase of the study. During this phase hotels were screened based upon answers given. in response to a questionnaire, and the results obtained from an initial total coliform test. The criteria used to select the hotels which were to take part in this study included the number of rooms available, allowing for grouping into large, moderate, and small categories; the total number of cisterns in the hotel, since one of the objectives was to study the total water quality of a selected hotel or guest house, (hotels or guest houses which had more than three cisterns were excluded); source/s of water in the cistern, as we wanted a representative sample of the most common water sources; disinfection practice and frequency; compliance or non-compliance with the testing regulation; and finally the results of the initial total coliform screen to see if any problem was existent. Based upon the results of this information, eleven hotels and guest houses were selected. Four were large hotels having more than 100 rooms, with a total of 6 cisterns; three were moderately sized hotels having between 30 and 99 rooms, with a total of 5 cisterns; and four were small guest houses having less than 30 rooms, with a total of 6 cisterns. The project thus consisted of a study of water samples from eleven hotels and guest houses containing a total of 17 cisterns over a 11 month period. Within the selected study population 6 out of the 11 hotels studied (L 2 thru 4; M 3; and S 2,3) were tied directly into the potabie water line which allows these owners/operators to simply open a valve to fill their cisterns as the water demand dictates. Five of the hotels (L 2; M 1,2; and S 3,4) relied upon trucked water to supply their needs. These hotels during the month of October and the first half of November, and then again from mid April to July -- months which correspond to the “off season" when there are fewer tourists ~- did not tend to use as much water as during the "tourist season", mid November to mid April, when most of these hotels reported as constantly having to order water. Only hotel L 1 was totally self sufficient for their water needs relying upon Reverse Osmosis (R.0O.) to provide their water needs. Hotel M 2 was in the process of installing an R.O. unit for their needs, but had to also rely from time to time on trucked water. Hotel S 1 did not initially use its cistern water, which is a mixture of well and rain water, for drinking purposes, choosing to rely on bottled water for those needs, but did use it for washing and bathing. Towards the end of the study they installed a small carbon-based and silver-impregnated filter system in an exploratory attempt to get away from the expense of bottled water. All hotels were equipped to gather rainwater. Table 1 presents a summary of the results from the questionnaires from the 11 hotels. snonuT3uoD = sUuTIOTUO = “TO “ZUOO. RUBTT 3eTOTA eP4RTA “ATA etqeottddy ON = “°W'N *VUSWSATOAUT ASUMO WOAF 4oUu !zejem peseyoand uT quesead Tenptsetr suTaoTYyo = UOTRZeUTAOTYO eaAtssed TD BsATSsed ea LO A uo SkemtTy “AO/K pexyonaL/utey 000‘89 Oc-T Z St vs on pexyonaL On A SATSSSed ToO/R eT qe jog /utTey 000‘9% OOT T at € $s “WN N SATSSEed N ST qe od /uTey 000‘02¢ Le iA St és dA A “WIN. N TIOEM/UTeY 000/09 o€ T et TOS OW A SATSSEd TO/K eTqejod /uTey 000‘€C8 OT-MEBN T-ORUTH+¢ OS CW . "Oru. . OW A 3uU0D TO/R pexyonaL/utey O000‘'OSL oT T TS ZW OW OW A BSATSSEd TO/A peyonay/utey “TTeseun O?¢ c 6V TW OW R yn /TE TO/K aTqezod /utey 000'PET Oc~2 T-O4UT~Z BES v uTer eg OW A sATSSed TO/R eTqeqog /utey 000‘9S 6 THOQUT~-~ OST CT -aM eTqeyod OW R BATssed TO/K peyoniy/uteu “TTeaeug Oc € OLT 27 *4sTd On A ZUOD TO/R ‘ov u/uTeY 000‘9LE €Z-MSN T[-OQUT=€ OO€ TT usqzO pa yseL usazo qusUzeeLL s/aoinos (*Teb) (°saA) aI AO ATSAeM MOH AaReEM TORUeM Ajpoerdea °4STO ‘asto ¢ suyy # TSO UISISTO jo aby sesnoy 4senb/sjrzosea/s[Teqoy payoetTes ut ejJep pezepTer-TseVZeEm pue ULSEASTO 2T eTqeL Sample collection procedures. Sample sites were divided by geographic location intc three groups of five or six cisterns each. One group was sampled each week with. the others being sampled in rotation. The average number of samples collected from the large, moderate and small size hotels were 6, 7 and 6 respectively. The dates on. which samples were collected is shown in Appendix A. Samples were collected in sterile 1 liter, clear borosilicate glass, wide mouth bottles with ground glass stoppers. Each bottle contained 0.8 mL of a 10% solution of the dechlorinating agent sodium thiosulfate (1,3)). ~Samples were collected in accordance with Standard Methods for the Examination of Water and Wastewater (1). They were transported pack to the laboratory in light protected containers. Samples were not chilled upon collection as analysis usually commenced within 2.5 hours of collection. All samples held over 6 hours were discarded to ensure the reliability of the data. While it has been noted that die off does occur even after only short intervals (21,22), the die off has been shown to be insignificant for the times involved (33). Physical-chemical analyses. Measurements for free residual chlorine were performed on site by the DPD method (1) at the time of collection; measurements for pH, turbidity, conductivity were done upon arrival back at the laboratory, and in accordance with Standard Methods. Microbiological analyses. Analyses for total coliform, fecal coliform, fecal streptococcus, Pseudomonas aeruginosa, and overall heterotrophic plate counts were performed on each sample. Total coliform, and fecal coliform analysis were performed in accordance with both Standard Methods (1), and Microbiological Methods for Monitoring the Environment: Water and Wastewater (3). All analyses with the exception of the heterotrophic plate count were done via the membrane filter (MF) technique. The heterotrophic plate count was done using the spread plate technique. Total coliform, fecal coliform, and. fecal streptococcus were isolated on m-Endo Agar (Difco Laboratories, Detroit, MI) (1,2,3), m-FC Agar (Difco) (1,2,3), and KF Streptococcus Agar (Difco) (1,2,3), respectively, The heterotrophic plate count (1) was performed using Standard Plate Count Agar (Difco). All media were prepared in accordance with the manufacturer’s instructions. Analysis for Ps. aeruginosa were performed by non-standard methods as described below. Sample volumes of 100, 50, 25, and 10 mL were filtered. Total coliforn, fecal streptococcus (1,2,3), and Ps. aeruginosa (7,18) samples were filtered through 0.45 u filters (GN-6, 66068; Gelman Sciences Inc., Ann Arbor, MI.). Fecal coliform samples were filtered through 0.7 Uu filters (Millipore Corporation, Bedford, Mass.) (1). O.1 and 1 mL volumes of 3 dilutions ranging. from 1 to 10-© were run in duplicate for the heterotrophic plate counts. Total coliforms, fecal streptococcus, and the heterotrophic plate counts were incubated at 35 + 0.5°C (1,3). Fecal coliform plates were incubated at 44.5 + 0.2°¢ (1,3). Total coliforms and fecal coliforms were incubated for 24 hours; fecal streptococcus, and heterotrophic plate counts were incubated for 48 hours (1,3). Pseudomonas aeruginosa analysis. Ps. aeruginosa was isolated on. a new medium, m-CX agar, developed in this laboratory (29), but is based on a modification of the highly successful formula of King et al (15). The Ps. aeruginosa plates were preincubated at 30 + 0.5 °c for 3-4 hours and then incubated at 41.5 + 0.5 Sc (7,13,18,29) for the remaining 44 hours. Verification of isolates. Up to five typical and, if present, five atypical colonies were picked from each medium for each sample, and subjected to verification (3). Colonies were counted with the aid of a variable magnification dissecting scope with a minimum magnification of 10x (Parco EMZ745 -40L with annular fluorescent illumination; Parco. Scientific Co., Bienna, OH) (1,3). The heterotrophic plate counts were counted with the aid of a Quebec Colony Counter (1,3). 10 Typical green sheen, and atypical red colonies were picked from the m-Endo Agar plates and verified in Lauryl Tryptose Broth (Difco) and Brilliant Green Bile 2% (Difco) (1,3). Typical blue and atypical gray or blue-gray colonies from the m-FC Agar plates were verified in Lauryl Tryptose Broth and EC Medium (Difco) (1,2,3). Typical red-pink to red colonies from the KF Streptococcus Agar plates were verified for growth in Brain Heart Infusion Broth (Difco) at 35 and 44.5 + 0.2° C; for growth in Brain Heart Infusion Broth with 40% Bile, and by the Catalase test (1,2,3). Typical fluorescent yellow to yellow green or blue green, mucoid colonies and atypical small, clear, flat, non-mucoid colonies, were picked from the m-CX Agar plates (15,29) and verified on Skim Milk Agar (Brown and Foster) (1,7,18), Pseudomonas Isolation Agar (Difco)(6), and King’s B medium (15) (same as Difco’s Pseudomonas F Agar) (6). il RESULTS To maintain anonymity, each cistern studied is identified only by number (e.g. L 1-3 for cistern 3 in large hotel 1). Table 2 presents the number of times each site was sampled as well as the average data over time for total. coliform, fecal coliform, fecal streptococcus, Pseudomonas aeruginosa, and heterotrophic plate counts for each hotel cistern, broken down by class, as well as the average value for each parameter per class. The range of values for these parameters in each cistern are reported in Appendix B. From Table 2 we find that of the 17 cisterns studied, 12 on average failed the SDWS of < 1 total coliform per 100 mL; sixteen of the cisterns, however, met the standard at least once. Of the 12 cisterns which failed the total coliform standard on average, 8 had significant total coliform problems (an average total coliform count greater than 10), and of those eight, 6 showed significant fecal coliform problems as well. It should be noted however that ten of the 17 cisterns had fecal coliforms present and thus would have been in violation of an EPA limit of 0 per 100 mL had the proposed law been in effect. In addition 13 of the cisterns showed the presence of Ps. aeruginosa, of which 10 had levels which were > 10. 12 6 Table 2: Average bacterial counts in cistern waters of large (LL), moderate (M), and small (S) hotels. , 2 Cistern No. of Total@ Fecal@ Fecal@ Ps.# Standara® No. Samples Coliform Coliform Strep. aeruginosa Plate’ Count L 1-1 8 3 ) 8 88 io 12387 L 2-1 6 fe) fe) 166 10 yer L 2-2 6 26 0 13 19 | a) 10 L 2-3 6 0 0 9 0 “155 L 3-1 6 1 1 24 OO 91 L 4-1 4 | 2 1 20 0 . 1452 6 5 0 40 20000 2464 M 1-1 7 6 2 4 2 ) ‘2767 M 1-2 7 282 12 15 o7 49113 M 1-3 7 106 ~=—“‘«~SS'C 61 135 a 34602. M 2-1 7 901 40 11 333.) 64284 M 3-1 6 18 38 104 ~ Loo 614 7 263 22 39 MA 24276 S 1-1 7 102 7 69 23 "2752 S 2-1 6 a , 1 2b . 115739 S 2-2 6 4 0 42 61 3972 S 3-1 7 16 0 10 816 _ 2010 S 4-1 6 115 6 11 «+598 21393 S 4-2 2 0 0 5 fi - No Data 6 40 2 26 | 250 9173 a = Counts per 100 mL. Large hotels/resorts (L): > 100 rooms b = Counts per mL. Moderate size hotels (M): 30-99 rooms Small hotels (S): < 30 rooms 13 Table 3 gives the average turbidity for each cistern in each class, the average pH, and conductivity. These data are included to show that the influence of these parameters in cistern water is minimal. From Table 3 we find that 82% of all hotel and guest house cisterns in this study meet the turbidity standard of less than 1.0 NTU. The pH data show that in general, cistern water is only slightly alkaline (a pH of 7.00 is considered neutral). The very low conductivity data shows that there is very little salt or dissolved solids present in the water. Table 4. presents a summary of the percentages of the samples which would meet the current SDWS of < 1 total coliform per 100 mL, a suggested fecal coliform standard of < 1 fecal coliform per 100 mL, a suggested heterotrophic plate count standard of < 500 total organisms per mL, and the relative occurrence of Ps. aeruginosa in these samples as well as in the absence of the total coliform. Note that the large hotels defined as those with more than 100 rooms most frequently met the SDWS, meeting the standard 60% or more of the time, while the moderately sized hotels defined as those with 30 .- 39 rooms were less consistent, meeting these standards between 43% and 60% of the time. The small hotels and guest houses were highly variable, ranging from 0 to 100% in meeting the standard. On average, they met the SDWS 59% of the time. The moderately sized hotels were consistent, meeting this standard 49% of the time, on average. 14 Table 3: Summary of pH, Conductivity, and Turbidity in Selected Hotel and Guest House Cisterns Average Values and (Ranges) Cistern pH Turbidity (NTU) Conductivity No. | (uMHO) L 1-1 6.79 (6.48 ~- 7.07) 0.37 (0.13 - 0.68) 341 (190 ~ 760) L 2-1 8.86 (8.26 - 9.46) 0.52 (0.28 - 0.70) 209 (165 - 260) L 2-2 8.64 (6.96 - 9.25) 0.72 (0.44 - 0.92) 222 (150 = 300) L 2-3 8.88 (7.92 - 9.41) 0.62 (0.30 - 1.16) 212 (160: ~ 298) L 3-1 7.62 (6.45 - 9.42) 1.28 (0.18 - 2.89) 215 (14s 5 299) L 4-1 6.99 (6.53 ~ 7.88) 0.82 (0.35 - 1.25) 198 (140 - 269) 7.96 (7.10 - 8.75) 0.72 (0.28 ~ 1.27) 233 (158 = 364) M 1-1 7.57 (6.75 - 9.15) 0.51 (0.25 - 0.98) 178 (125 - 240) M 1-2 7.93 (7.01 - 9.20) 0.61 (0.40 - 0.73) 271 (190 - 630) M 1-3 7.91 (7.10 - 8.72) 0.67 (0.25 - 1.58) 246 (180 - 500) M 2-1 7.91 (7.00 - 9.03) 0.58 (0.18 ~- 0.89) 710 (100 ~ 1200) M 3-1 7.91 (6.52 - 9.16) 1.08 (0.23 - 2.30) 212 (140 ~ 320) 7.85 (6.88 ~ 9.05) 0.69 (0.26 - 1.30) 323 (147 ~ 578) S 1-1 7.74 (7.61 - 7.85) 0.63 (0.27 - 1.34) 1424 (170,)- 1900) S 2-1 7.91 (6.83 - 9.06) 0.26 (0.11 -.0.38) 204 (160'- 240) S 2-2 7.88 (6.89 - 8.61) 0.40 (0.16 - 0.81) 299 (200 ~. 520) S 3-1 8.26 (7.00 ~ 9.10) 0.89 (0.47 ~ 2.65) 236 (180 - 339) S 4-1 7.49 (6.94 - 8.42) 0.43 (0.32 - 0.65) 177 (125. ~ 249) S 4-2 8.90 (8.90 - 8.90) 3.92 (1.28 ~ 6.55) 190 (180 ~ 200) 8.03 (7.36 ~ 8.66) 1.09 (0.44 ~ 2.06) 422 (169 - 575) Table 4: Summary of cistern water quality in selected large (L), moderate (M), and small (S) hotels & fo} o of 4 Los ° of 2 2. Q of & co o ce) oO of of samples + samples samples samples for Ps. aeruginosa samples Cistern meeting meeting meeting and (in the absence with Free Cl No. SDWS a FCS* a HPCS** of Total Coliform) i-1 63 86 75 29 (0) 88 2-1 100 100 75 17 (17) 100 2-2 86 100 50 17 (17) 100 2-3 100 100 75 17 (17) 100 3-1 86 83 100 O (0) 100 4-1 60 75 50 0 (0) 100 83% 91% 741% 13% (9%) 98% 1-1 50 771i 20 (14) 13 43 43 1-2 43 67 20 67 (17) 1-3 43 43 17 (17) 29 2-1 50 86 20 86 (43) 25 3-1 60 83 67 O (0) 100 49% 70% 25% 43% (18%) 42% 1-1 6) 14 ) 100 (0) 83 60 40 71 2-1 86 (33) 2-2 71 100 40 67 (50) 43 3-1 25 100 33 88 (14) 57 40 33 N.A 4-1 71 83 (0) 4-2 100 100 No data Q (0) N.A. 59% 80% 35% 55% (16%) 43% ee a suggested fecal coliform standard (< 1 per 100 ml) kk a suggested heterotrophic plate count standard (< 500. per mL) N.A. Not Applicable (ultra violet disinfection) 16 The opportunistic pathogen Ps. aeruginosa was found in 13 of the 17 or 76% of the cisterns at one time or another. rt also occurred in the absence of total coliforms. In large hotels Ps. aeruginosa was found in only 13% of the samples, while in moderate and small hotels, it was found in 43%, and 55% of the samples respectively. The occurrence of Bs. aeruginosa in the absence of total coliforms ranges from 9% in large hotel cisterns to 18% in the cisterns of moderate hotels. As a whole, of those hotel and guest house cisterns which tested positive for Ps. aeruginosa, 18% were .positive for the organism in the absence of total coliform. This figure matches with the data from our previous studies (29,31). of private homes and public housing projects. Table 4 also reveals the relative percentage of times free residual chlorine was found in each cistern. “he average values. and ranges are included as Appendix C. The large hotels were the most consistent in their chlorination practices, meeting the EPA guideline of at least 0.2 mg/L from 88% to 100% of the time, while the moderately sized hotels and the small hotels and guest houses had considerable variability. Chlorination is still the most effective way of reducing microbial growth. When there was treatment, there was an almost four fold increase in the number of samples which were contaminant free compared to samples which received ‘no treatment. When contaminants did survive the treatment 17 process, they tended to cluster in the low range whereas without treatment, they tended to cluster in the high range. Table 5 presents the occurrence of each contaminant in relation to the free residual chlorine present... It should be noted that the fecal streptococcus organism tended to be the most resistant organism to chlorination and could be found in cisterns with a residual of > 3.6 mg/L. Fecal streptococci can cause skin infections and respiratory diseases such as pneumonia, Sinusitus etc. Ps. aeruginosa too could be found frequently up to 1.0 mg/L, and occasionally up to 3.0 mg/L. This overall resistance may account for the presence of Ps. aeruginosa in the absence of total coliforms (23). Ps. aeruginosa can cause ear infections, urinary tract infection and diarrhea. Looking again at Table 5 we see that 69% of the occurrences of Ps. aeruginosa occurred in the absence of a chlorine residual. Only a small fraction occurred in the presence of a chlorine residual greater than 1.0 mg/L, yet it may well be that this same small fraction is also the one that is present when total coliforms are absent. Essentially their greater resistance to stress in the environment allow them to survive after the off, either naturally, or from Qu coliforms have die disinfection practices (23). is Table 5: Occurrence of Contaminants in Relation to Free Residual Chlorine o ~— — Free Cla 0.0 0.2 1L.G - i &s 2.0 2.2 3.0 3.2 3.6 No Contam. b 8 20 Total 28 12 Coliform b Fecal Coliform b 17 2 Fecal 21 17 Strep. b Ps. aeruginosa b 29 a Free chlorine residual in mg/L (ppm) b Number of samples positive for the indicated organisms in the given chlorine residual ranges Again, as in. past studies (29,30,31), we have looked at the ratio and fecal streptococcus. This of fecal coliform to excrete fecal ratio is based on the fact that an tends coliforms in while greater numbers than fecal streptococcus, animals tend to excrete greater numbers of fecal streptococcus than fecal coliforms (1) Fecal coliforms indicate the possible presence of enteric pathogens such as Salmonella, SoG Shigella etc.; Salmonella Can cause disea wa such as typhoid. 19 Based upon the ratio of fecal coliforms to fecal streptococci, one is able to, in theory, not only identify the area from which the pollution is occurring, but the source of the pollution as well. In general, however, ratios in excess of 4.1 are taken to indicate a predominantly human origin of the coliform bacteria. Ratios less than 0.7 are taken to indicate pollution from non-human sources. Ratios between 0.7 and 4.1 usually indicate wastes of mixed human and animal sources (1,2). Normally fecal coliform/fecal streptococcus ratios are applied to water quality studies of lakes, streams, and estuaries; our purpose for doing these ratios however is one of a qualitative and not quantitative nature. The use of these ratios is not intended to pinpoint an exact source or point of contamination, but rather to aid in determining whether any observable contamination is essentially due to environmental contamination, or whether there might be septic tank infusion. From Table 6 it becomes clear that since both the fecal coliform/ fecal streptococcus ratios are low, and the fecal streptococcus counts are less than 100, the source/s of the contamination is of environmental, rather than anthropogenic origin, and is consistent with our previous findings (29,31). 20 pouTwrejed FON >peqyaodez eae snooos0qdszqjs [eoey suo ueYR eTOW 10 WIOJTTOD Teosey suo ueyR sAow Hhututequoo seTdwes ATUO “TU OOT aed uaath exe squnop eB 00°0 S 0 fe) 68/LZ/E0 @-b S 62°83 L 8g 6C2 68/50/90 €-T W Z0°O OS t vos 68/61/90 t-7 Ss €0°0O TVe TL 86 68/€0/%0 c-T W 00°0 € ) 0 68/LZ/E0 T-' S$ T9°O 99 OV S6 68/PT/C0 €-t W 00°0 ot 0 T 68/L2/Z0 T-?7 S$ 00°0 6 0 ) 68/TC/TO c-1I W 0O°SE T S¢ Zz 68/€Z/T0 T-) S$ 00°? T Z PTl 68/9T/TO €-t W 00°0 vt fe) Lt 68/E1T/P70 T-€ S q°a'n 0 O€ €St 68/50/90 Z-t W 00°0 09 0 v 68/L0/Z0 T-c $s 6S°0O v6 GG 8S 68/¥PT/EO Z-T W 00°O € 0 ) 68/TT/LO 7-2 S 00°O €T 0 0 68/TE/TO t-1t W 00°O Z9 fe) 0) 68/ET/ZO t-2 S GO°O TZ. T Lt 68/ET/VO T-T W 00°O SPT 0 6 68/0€/T0 @-2 Ss oo°L z PT z 68/¥T/E0 T-t K 00°0O 6Y 0 T 68/ET/Z0 T-2 Ss 00°0 9 0 v 68/T€/T0 T-T W GO°O 8S € S 68/0€/TO T-2 S GO°O 6S € € 68/TE/TO T-' 1 q°a'N 0 S et 68/92/90 T-T Ss 00°0O 6 fe) @) 68/T2/E0 T-€ 7 62°? eT Ze 9 68/0€/G0 T-T S$ 00°0O Sct 6) 0 68/L0/Z0 T-c 00°0 zt ) Et 68/0T/¥0 T-I S$ pro 6 v 9 68/LT/TO T-c€ 7 vO°O GG Zz OL 68/CT/E0 T-1 Ss 00°0 v ) 0 68/TT/t0 €-% I TO’O LOE Zz GZ 68/L0/Z0 T-1T S 00°0 8z ) @) 68/¥T/Z0 €-2 TI TT’O 9€ v Ose es/60/TT T-T S$ 00°0 T2 () ) 68/%2/TO €-2 I ot‘o 09 9 yt72 88/62/0T T-T S 00°O LS 0 fe) 68/TT/P0 Z-2 T 00°0O LZ9 ) Zz 68/L7/€O0 I-€ W 00°0 Tt 0 ) 68/¥#T/Z0 7-2 TI 00°O v? a) ) 68/€T/Z0 T-€ W 00°O 8st 0 0 68/%2/TO z-e2 I 60°? 9S 622 Let 68/LT/TO T-¢ W 00°0 9 a) fe) 68/TT/P0 T-e I q°a°n fe) v8z 007¢< 68/50/90 T-@ W 00°O OPTt fe) T 68/1/70 T-2 1 00°0 Tl 0 09€c9 68/0T/¥0 T-¢ W 00°0O oT fe) fe) 68/%2/T0O T-2 I 70°O 92 T T 68/90/£0 T-2 W 00°O 8 ) 9T 68/0T/%0 [T-T I 00°0O SE ) Zz 68/90/20 T-2 W 00°0 S 0 0 68/90/£0 T-T I 00°0 Zz ) O2T 88/3z2/0t T-2 W S0°O Cv Zz v 68/90/20 T-1 7 otjzey ‘dezys waoxytt~op waoejytptoo aed “ON otTzey “dezqyg WACJTTOD warzoejxtTyToo ayeg "ON sa/oq epleoeg eTeoe4 STEROL etTdues uzeqysto sd/od epTeosg eTeodsy eTeqoL etTdues uze4sto snoos0004deazy4s [eosy Of WAOCFTTOD [Teoseyg Jo sotqey :9 eTqeL 21 DISCUSSION The water quality of hotels and guest houses varied greatly. The large hotels that were sampled were in compliance with the SDWS more after than the small and moderate sized hotels and guest houses. Of the nine hotels which filled their cisterns either from the potable water lines and/or purchased (trucked) water, seven relied at least to some extent. on passive chlorination -- that water sold either directly or indirectly by the Virgin Islands Water and Power Authority (WAPA) containing free residual chlorine as a result of their chlorination practices, and not due to. any effort on the part of the purchaser. Indeed for at least two of those hotels and guest houses (S-2, M-3) that was indeed the only chlorination that the water received. Thus the cistern water quality of those hotels which rely entirely or in part on WAPA’s chlorination practices will be to Some degree suspect for two reasons: Should WAPA for any reason fail to chlorinate their water supply, the water entering the cistern could very well be contaminated (8,20,27,31). if the water has a slow turnover rate of consumption, any initial free residual chlorine will either be used up and/or liberated to the air, which is usually within 3-5 days (29); thereafter the water is susceptible te either regrowth due to bacterial contaminants from within the system ~~ which could come from either the bottom sediment sludge usually found in cisterns or from any suspended turbidity particles in the water column -- or from new input due to a rainfall (29). 22 Chlorination is still the cheapest and most reliable source for disinfection (10,20,24,26); yet chlorination for all its effectiveness does not guarantee that the water will be safe to drink (20). Factors such as turbidity, pH, and bacterial adaptations play a role in overall chlorination efficiency. Bacteria such as Bacillus, an aerobe, and Clostridium, an anaerobe can form spores which can withstand chlorination (9); some bacteria are naturally resistant, while others contain plasmids which can convey resistance; other organisms such as viruses and protozoa show various patterns of resistance to chlorination. Turbidity too plays a role (12,32). Turbidity in the water allows bacteria to clump onto a particle, with some bacteria atop other bacteria. During chlorination the outer most bacterial layer will be killed, while others towards the center of the particle may survive to go on to recontaminate the water, even though it has been treated. The particle can also react with the free chliorine thereby reducing its concentration. What chlorination does do is provide a high degree of probability that the water will be safe to drink, since the vast majority of microorganisms are susceptible to its effects. Enforcement of the provisions of the SDWA, while not a guarantee about the overall safety of drinking water supplies, goes a long way towards that goal. Lax enforcement of those laws for whatever reasons allows room for noncompliance situations to develop. New EPA regulations governing water 23 guality will come into effect in 1991 and many public health microbiologists feel these amendments are long overdue; however, these additional regulations will mean additional expense. While most hotels will be able to meet the new fecal coliform standard, few will be able to consistently meet the new heterotrophic count standard if our results are any indication. The additional expenses coupled with be a greater number of samples which are likely to be in non-compliance can only serve to increase the likelihood that there will be more hotel and guest house owners/operators who may try to forgo having their water tested. The best way then to address the potential problem is to encourage voluntary compliance by establishing meaningful cistern water quality standards such as testing for fecal coliform, Ps. aeruginosa and standard plate count. 24 SUMMARY About one-haif of the cisterns exhibited a significant presence of total coliforms. Approximately one-third of the cisterns showed the presence of fecal coliforms. We believe that the fecal coliform count is a better indicator of true risk than the currently used total coliform count because of the largely non-anthropogenic (non human origin) coliform contributions found in cistern water supplies. The total coliform may therefore not be the most appropriate indicator for cisterns. Ps. aeruginosa was found in 76% of the cisterns; 18% of those samples contained Ps. aeruginosa in the absence of total coliform. These data agree remarkably well with our prior studies done on the cistern water quality in private homes (29) and in public housing projects (31). Most of the hotels and guest houses in this study had pH values and turbidity readings well within acceptable ranges. Probably the biggest problem for cistern water users, especially those who supply water to the public, is turbidity due to resuspension. In places which use a lot of water, the turnover time for the water in the cistern is short; as the water level falls, any disturbance of the sediment layer, will tend to resuspend debris in the water column, leading to non- compliance for turbidity. 25 RECOMMENDATIONS The following recommendations are made based upon both laboratory results, and from information obtained from EPA and hotel owners/operators: 1. Realistic water quality regulations should be established to cover cistern water systems. These regulations should be specific and reasonable in scope, yet should provide adequate protection to public health. 2. The Virgin Islands Water and Power Authority should expand their water testing procedures, so that samples are not only collected from the main potable water line, but from each of its major branch lines as well. These samples should be tested for both total coliform and heterotrophic bacteria. 3. Hotel and guest house owners/operators should be required to test water on a quarterly basis for fecal coliform and Pseudomonas aeruginosa. 4. Hotel and guest house. owners/operators should test water on a daily basis for turbidity and chlorine residual, © and additional chlorine should be added if it is less than 0.2 mg/L. 5. If chlorination is not used for disinfection purposes, | the hotel or guest house owner/operator should submit a manufacturer’s statement of the effectiveness of the treatment process used as well as a daily log of use and maintenance. In addition, testing for fecal coliform and Pseudomonas aeruginosa should be done on a monthly basis. 26 10. BIBLIOGRAPHY American Public Health Association. 1985. Standard methods for the examination of water and wastewater, 16th Ed. American Public Health Association, Washington, Dc. Bordner H. Robert, Clifford F. Frith, and John A. Winter. 1977. Symposium on the recovery of indicator organisms employing membranes filters. EPA-600/9- 77-024. Environment Monitoring and Support Laboratory, Office of Research and Development, U.S. Environmental Protection Agency Cincinnati, Ohio. Bordner, R. and J. Winter (ed.). 1978. Microbiological methods for monitoring the environment. U.S. Environmental Protection Agency, Cincinnati, Ohio. Bott, T.L. 1973. Bacteria and the assessment of water quality, P11-75 In ASTM STP 528, Biological methods for the assessment of water quality. American Society for Testing and Materials, Washington, DC. Craun, G.F. 1978. Impact of the coliform standard on the transmission of disease, p. 21-35. In Charles W. Hendricks (ED.) Evaluation of the microbiology standard for drinking water. U.S. Environmental Protection Agency, Washington, DC. Difco Laboratories. 1984. Difco manual, 10th Ed. Difco Laboratories, Detroit, MI. Dutka, B.J., and K.K. Kwan. 1977. Confirmation of the single-step membrane filtration procedure for estimating Pseudomonas aeruginosa densities in water. Appl. Environ. Microbiol. 33:240-245. Evans, M.T., M.W. LeChevallier, C.E. Waarvick, and Ramon J. Seidler. 1981. Coliform species recovered from untreated surface water by the membrane filter, standard, and modified techniques. Appl. Environ. Microbiol. 41:657-663. “Freeman, Bob A. 1979. Burrows textbook of microbiology. 21st Ed. W.B. Saunders Company. Philadelphia, London, Toronto. Geldreich, Edwin E. 1986. Control of microorganisms of public health concerns in water. J. of Environ. Sci. 28:34-37. 27 ll, i2. 13. 14. 15. 16. 17. 18. 19. 20. Geldreich, E.E., B.A. Kennwer, and P.W. Kabler. 1964. Occurrence of coliforms, fecal coliforms and streptococci on vegetation and insects. Appl. Microbiol. 12:63~69. Herson S. Diane and Hugo T. Victoreen. 1980. Hindrance of coliform recovery by turbidity and non-coliform. Municipal Environmental Research Laboratory Office of Research and Development Protection Agency Cincinnati, OH. Hugh, Rudolph and Gerald L. Gilardi, 1980. Pseudomonas, P. 288-317. In. Edwin H. Lennette (ed.). Manual of clinical microbiology, 3rd ed. American Society of Microbiology, Washington, Dc. Isquith, Irwin R. and Harvey Winters. 1981. Microbial analysis of domestic cistern water in the U.S. Virgin Islands. Technical Report No. 7, Caribbean Research Institute, University of the Virgin Islands, St. Thomas, VI. King, Elizabeth 0O., Martha K. Ward, and Donald E. Raney. 1954. Two simple media for the demonstration of pyocyanin and fluorescin, J. Lab. Clin. Med. 44:301- 307. Kooij D. Van Der., J.P. Oranje, and W.A.M. Hijnen. 1982. Growth of Pseudomonas aerginosa in .tap water in relation to utilization of substrates at concentrations of a few micrograms per liter. Appl. Environ. Microbiol. 44:1086-1095. Lechevallier W. Mark and Gordon A. McFeters. 1985. Interactions between heterotrophic plate count bacteria and coliform organisms. Appl. Environ. Microbiol. 4971338-1341. Levin, M.A. and V.d.. Cabelli. 1972. Membrane filter technique for enumeration of Pseudomonas aerginosa. Appl. Microbiol. 24:864-870. Lye, Dennis J. 1987. Bacterial levels in cistern water systems of Northern Kentucky. Water Res. Bull. 23: 10063-1068. McCabe, LeLand J. 1987. Chlorine residual substitution rationale, p. 57-63 In Charles W. Hendricks (Ed.) Evaluation of the microbiology standard for drinking water. U.S. Environmental Protection Agency, Washington, DC. 28